RIELLO UPS SEP3000ER 3000VA
Rated power: 3000 VA
Voltage: 220 / 230 / 240 V
Voltage tolerance: 230 V ±20%.
Frequency. 50 / 60 Hz
Frequency tolerance: 50 Hz ±5% / 60 Hz ±5%.
Power factor: >0.99
Current distortion: ?7%.
Voltage tolerance: 180 / 264 V
Frequency tolerance: Frequency selected (±1.5 Hz to ±5 Hz configurable)
Rated power: 3000 VA
Active power: 2400 W
Number of phases: 1
Crest factor (Ipicco/Irms): 3 : 1
Waveform: Sinusoidal
Frequency: Selectable: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorting load: <4%.
Voltage distortion with linear load: <2%.
Overload times
Load = 150%: 1 sec.
Load = 125%: 5 sec.
Batteries
Type: VRLA AGM lead-acid, maintenance-free; Supercaps
Charging time: 2-4 h
Colour: Black
Dimensions: 190 x 446 x 333 mm
Weight: 15 kg
- Phase
- Single phase
- Frequency (Hz)
- 50 / 60
- Voltage (V)
- 220 / 230 / 240
- Power (VA)
- 3000
- Battery type
- VRLA/AGM/GEL/NiCd/Liion/Supercaps
- Operating temperature (°C)
- 0 °C / +40 °C
- Length (mm)
- 446
- Width (mm)
- 190
- Height (mm)
- 333
- Dry weight (Kg)
- 15
- Colour
- Black
CHARACTERISTICS
Filtered, stabilised and reliable voltage: ON LINE double conversion technology (VFI according to IEC 62040-3) with filters for atmospheric noise suppression;
High overload capacity (up to 150%);
Programmable auto restart at mains return;
Battery ignition (Cold Start);
Load power factor correction (UPS input power factor close to 1);
Wide input voltage tolerance range (from 140 V to 276 V) without battery intervention;
Expandable autonomy for several hours;
Fully configurable via UPS Tools configuration software;
High battery reliability (automatic and manually activated battery test);
High UPS reliability (total microprocessor control);
Low impact on mains (sinusoidal absorption).
ADVANCED COMMUNICATION
Multiplatform communication for all operating systems and network environments: PowerShield3 monitoring and shutdown software for Windows 10, 8, 7, Hyper-V, 2019, 2016, 2012 and earlier versions, Mac OS X, Linux, VMWare ESXi, Citrix XenServer and other Unix operating systems;
UPS Tools configuration and customisation software supplied as standard;
RS232 serial port and opto-isolated contacts;
USB port;
Slot for communication cards.