UPS300 Three-phase - Nominal power 30 KVA P.F. 0.8
INPUT
Nominal power: 30KVA
Voltage: 380/400/415 VAC three-phase + N + ground
Input voltage variation: ± 20%
Frequency: 40 / 72 Hz
Power factor: 0.99
Maximum input current phase/neutral: 45 A
Harmonic distortion:< 3%
BY - PASS
Rated voltage: 380/400/415 VAC three-phase + N + earth
Voltage variation: ± 15% (selectable from ± 5% to ± 25%)
Frequency: 50/60 Hz
Rated current: 200% In
Number of phases: 3+N
Protection: short circuit - over load - over temperature
OUTPUT
Nominal power: 30 KVA
Active power: 24 KW
Number of phases: 3+N
Crest factor:3:1
Waveform: sinusoidal
Static stability: ±1%
Dynamic stability: ± 1%
Phase/neutral output current: 38 A
Frequency: 50/60 Hz selectable and/or automatic
Distortion on linear load: 1%
Non-linear load distortion: 3%
Dimensions mm: 500 x 800 x1100 h
Weight without batteries in Kg: 115
Weight of metal cabinet in Kg: 150
- Phase
- Three phase
- Frequency (Hz)
- 50 / 60
- Voltage (V)
- 380/400/415 trifase + N + terra
- Protection degree
- IP21
- Power (VA)
- 30000
- Full charge time in network (h)
- 6
- Battery type
- Maintenance-free hermetic lead
- Length (mm)
- 800
- Width (mm)
- 500
- Height (mm)
- 1100
- Sound level at driver's ear
- ? 50 dBA
- Input voltage (V)
- 380/400/415 trifase + N + terra
- Kind of wave
- Sinusoidal
- Colour
- Black
- Nominal input voltage (V)
- 380/400/415 VAC trifase + N + terra
- Display/read-out
- LCD display
- Approvals
- EN 62040 - 2 Lev. A and Directive 73/23 EEC, 93/68 EEC, 89/336 EEC
- Power factor control
- 0.99
- Protections
- Over temperature, over load, short circuit, high/low battery voltage
- MasterBus compatible
- Yes
- Weight (Kg)
- 150