UPS300 Three-phase - Nominal power 30 KVA P.F. 0.8

UPS300 Three-phase - Nominal power 30 KVA P.F. 0.8
search
  • UPS300 Three-phase - Nominal power 30 KVA P.F. 0.8
  • UPS300 Three-phase - Nominal power 30 KVA P.F. 0.8
UPS 300
New product

INPUT
Nominal power: 30KVA
Voltage: 380/400/415 VAC three-phase + N + ground
Input voltage variation: ± 20%
Frequency: 40 / 72 Hz
Power factor: 0.99
Maximum input current phase/neutral: 45 A
Harmonic distortion:< 3%
BY - PASS
Rated voltage: 380/400/415 VAC three-phase + N + earth
Voltage variation: ± 15% (selectable from ± 5% to ± 25%)
Frequency: 50/60 Hz
Rated current: 200% In
Number of phases: 3+N
Protection: short circuit - over load - over temperature
OUTPUT
Nominal power: 30 KVA
Active power: 24 KW
Number of phases: 3+N
Crest factor:3:1
Waveform: sinusoidal
Static stability: ±1%
Dynamic stability: ± 1%
Phase/neutral output current: 38 A
Frequency: 50/60 Hz selectable and/or automatic
Distortion on linear load: 1%
Non-linear load distortion: 3%

Dimensions mm: 500 x 800 x1100 h
Weight without batteries in Kg: 115
Weight of metal cabinet in Kg: 150

Technical features
Phase
Three phase
Frequency (Hz)
50 / 60
Voltage (V)
380/400/415 trifase + N + terra
Protection degree
IP21
Power (VA)
30000
Full charge time in network (h)
6
Battery type
Maintenance-free hermetic lead
Length (mm)
800
Width (mm)
500
Height (mm)
1100
Sound level at driver's ear
≤ 50 dBA
Input voltage (V)
380/400/415 trifase + N + terra
Kind of wave
Sinusoidal
Colour
Black
Nominal input voltage (V)
380/400/415 VAC trifase + N + terra
Display/read-out
LCD display
Approvals
EN 62040 - 2 Lev. A and Directive 73/23 EEC, 93/68 EEC, 89/336 EEC
Power factor control
0.99
Protections
Over temperature, over load, short circuit, high/low battery voltage
MasterBus compatible
Yes
Weight (Kg)
150
Details
* Images and technical data are not binding. Please always consult the manufacturer's technical data sheet. Manel Service assumes no responsibility for any changes made by the manufacturer or any typographical errors.
Technical Sheet / Manuals
Related Accessories
Ask for availability
Add to wishlist
Download PDF
Ask a question
Product: UPS300 Three-phase - Nominal power 30 KVA P.F. 0.8
Offer on letterhead
Product: UPS300 Three-phase - Nominal power 30 KVA P.F. 0.8
Technical features
Phase
Three phase
Frequency (Hz)
50 / 60
Voltage (V)
380/400/415 trifase + N + terra
Protection degree
IP21
Power (VA)
30000
Full charge time in network (h)
6
Battery type
Maintenance-free hermetic lead
Length (mm)
800
Width (mm)
500
Height (mm)
1100
Sound level at driver's ear
≤ 50 dBA
Input voltage (V)
380/400/415 trifase + N + terra
Kind of wave
Sinusoidal
Colour
Black
Nominal input voltage (V)
380/400/415 VAC trifase + N + terra
Display/read-out
LCD display
Approvals
EN 62040 - 2 Lev. A and Directive 73/23 EEC, 93/68 EEC, 89/336 EEC
Power factor control
0.99
Protections
Over temperature, over load, short circuit, high/low battery voltage
MasterBus compatible
Yes
Weight (Kg)
150