Contacts: +39 011 25 35 33 - info@manelservice.com
Three-phase maximum power: 1100 KW
Three-phase continuous power: 1000 KW
Three-phase maximum power: 1375 KVA
Three-phase continuous power: 1250 KVA
Fuel: Diesel
Voltage: 400 V + N
Frequency: 50 Hz
Current: 1805 A
Power factor cosφ: 0.8
Electrical protection: IP44
Engine: PERKINS 4012 46TWG2A
Displacement: 45842 cc
Engine speed: 1500 rpm
Bore x stroke: 160 x 190 mm
Aspiration: Turbo
Speed governor: Electronic
Number and arrangement of cylinders: V12 60°
Cooling system: Water
Starting system: Electric
Alternator: MARELLI MOTORI, brushless
Poles: 4
Voltage regulator system: AVR
Consumption: 196 L/h at 75% load / 259 L/h at 100% load
Tank capacity: 400 L
Autonomy: 2 h at 75% load
Sound pressure level: 70 dB(A) at 7 m
Length: 12192 mm
Width: 2438 mm
Height: 2896 mm
Weight: 11500 Kg
Data sheet
Specific References
These generator sets are equipped with diesel engines from Lombardini, Kohler, Perkins, FPT, Doosan, Deutz, and Volvo, with electric start and battery, coupled by bell housing and flexible coupling, mounted on a fixed base with anti-vibration mounts and a fuel tank integrated into the base frame.
Manual control panel mounted on the unit, equipped with the following instrumentation: circuit breaker protection, voltmeter, 1 or 3 ammeters (depending on power), counter, frequency meter, ignition key, visual indicators for low oil pressure, high coolant temperature, battery charging alternator, low fuel level, with automatic shutdown in case of faults, and socket or terminal board for use.
On request: automatic panels, slow or fast towing trolleys (for registration), protective canopies, soundproof canopies, special configurations.
Available alternators: Linz Electric, Marelli Motori, Stamford (Mecc Alte only on request with surcharge).
* Images and technical data are not binding. Please always consult the manufacturer's technical data sheet. Manel Service assumes no responsibility for any changes made by the manufacturer or any typographical errors.